Isolated RS485 hub that splits one RS485 bus into four independently isolated channels, so a fault or surge on one branch never takes down the rest of the network. 5000 Vrms isolation, 300 bps to 5 Mbps, 9–36 VDC input, 35 mm DIN rail mounting, and −40 °C to +85 °C operation. Built for PLCs, BMS, energy metering and industrial control panels.
Isolated RS485 hub for control networks that can’t afford downtime. The DTECH IOT9024DI takes one RS485 bus and splits it into four independently isolated channels, so a surge, ground loop or wiring fault on one branch stays on that branch instead of taking down every device on the line.
Built for control panels, BMS risers and factory floors, this 4-port isolated RS485 hub gives system integrators and electrical contractors a clean way to turn a long, fragile daisy chain into an organised star layout. Each output becomes its own protected segment, which makes faults easier to trace, devices easier to add, and the whole network more resilient in harsh electrical environments.
RS485 is the backbone of industrial serial communication, carrying Modbus RTU, BACnet MS/TP and many proprietary protocols between PLCs, meters, drives, sensors and controllers. A standard RS485 bus has one weakness: everything shares one cable. One shorted device, one lightning-induced surge, or one ground potential difference between buildings can corrupt data or damage every node on the line.
An isolated RS485 hub solves this by electrically separating each branch. With 5000 Vrms isolation and independent isolation between channels, the IOT9024DI breaks ground loops, blocks surges from travelling across the network, and keeps a problem on one branch from spreading to the other three. For anyone maintaining a site, that means less downtime and faster fault-finding.
1 RS485 input to 4 isolated RS485 outputs: expand one master port into four separate branches without rewiring the whole network.
5000 Vrms isolation: protects controllers, PLCs and expensive field devices from surges, ground loops and electrical noise.
Independent channel isolation: a fault on one branch does not interrupt communication on the others.
300 bps to 5 Mbps data rate: covers slow legacy meters through to high-speed RS485 links on a single device.
Long-distance communication: up to 1,200 m at 115200 bps (reference figure; actual distance depends on cable, topology, termination and the electrical environment).
Common-mode rejection above 70 dB: holds data integrity in noisy plant rooms near motors, VFDs and switchgear.
Wide 9–36 VDC power input: runs directly from standard 12 VDC or 24 VDC panel supplies, drawing only 0.4 W.
35 mm DIN rail mounting: clips straight into control cabinets alongside breakers, PLCs and terminal blocks.
Industrial temperature range of −40 °C to +85 °C: suited to outdoor enclosures, rooftop plant and unconditioned Gulf installations.
Compact 64.5 × 27 × 90.5 mm housing: saves valuable rail space in crowded panels.
Brand: DTECH
Model: IOT9024DI
Product type: Industrial 4 port isolated RS485 hub
Ports: 1 × RS485 input, 4 × RS485 outputs
Isolation: 5000 Vrms, independent isolation between channels
Baud rate: 300 bps to 5 Mbps
Transmission distance: up to 1,200 m at 115200 bps (reference figure)
Common-mode rejection: >70 dB
Power input: 9–36 VDC
Power consumption: 0.4 W
Protection rating: IP40
Operating temperature: −40 °C to +85 °C
Operating humidity: 5–95% RH, non-condensing
Mounting: 35 mm DIN rail
Dimensions (L × W × H): 64.5 × 27 × 90.5 mm
PLC and industrial automation: connect one PLC serial port to four separate groups of drives, I/O modules or HMIs.
Energy and power metering: split a Modbus RTU line feeding multiple energy meters across different distribution boards.
Building management systems (BMS): separate BACnet MS/TP or Modbus branches by floor, riser or plant room so one faulty field controller doesn’t take down the building.
Sensors and monitoring equipment: run temperature, flow, pressure and environmental sensors on isolated branches.
Factory control cabinets: organise serial wiring inside panels and isolate equipment supplied by different vendors.
Solar, generator and UPS monitoring: link inverters, gensets and battery systems back to one data logger or SCADA gateway.
Serial network expansion: add new RS485 devices to an existing installation without lengthening an already overloaded bus.
Mount the isolated RS485 hub on a 35 mm DIN rail and power it from a 12 VDC or 24 VDC supply within the 9–36 VDC range. Connect the master device (PLC, gateway or SCADA port) to the RS485 input, then wire each branch to one of the four outputs. Use shielded twisted-pair cable, terminate the far end of each long branch, and keep RS485 runs away from high-voltage power cabling for the most reliable results. Because each output is its own segment, label branches by area so maintenance teams can isolate faults quickly.
For background on the standard, see this overview of RS-485 (https://en.wikipedia.org/wiki/RS-485) and the manufacturer’s product page (https://www.dtechelectronics.com/dtech-iot9024di-industrial-4-port-isolated-rs485-hub_p688.html).
[H2] Buy the DTECH IOT9024DI Isolated RS485 Hub in Dubai and the UAE
Bait Almajara Trading L.L.C. (BAM) is the Middle East distributor for DTECH, supplying system integrators, MEP and electrical contractors, facility management companies and procurement teams across the UAE, GCC, Africa and Central Asia. We offer project pricing, bulk quantities and technical support to help you choose the right isolated RS485 hub, converter or serial device for your site.
Explore more in our IoT and Industrial Serial range, including RS485 converters, serial-to-Ethernet servers and USB to RS485 adaptors.
For quotations or project enquiries, contact sales@bam.ae or WhatsApp +971 52 374 3008.
It takes one RS485 line and splits it into several separate branches, with electrical isolation between them. This lets you build a star layout instead of one long daisy chain, and stops surges or faults on one branch from affecting the others.
They are closely related. A repeater extends one line, while a hub or splitter divides one line into multiple branches. The IOT9024DI works as a 4-port RS485 splitter with isolation on every channel, and each branch can run long cable distances.
It works at the RS485 physical layer, so it carries common RS485 protocols such as Modbus RTU and BACnet MS/TP. Contact BAM to confirm suitability for your specific devices and baud rate.
[H3] What power supply does it need?
Any DC supply from 9 V to 36 V. Standard 12 VDC and 24 VDC control panel supplies both work, and the hub draws only 0.4 W.
[H3] Can it be installed outdoors or in hot climates?
It operates from −40 °C to +85 °C and 5–95% RH non-condensing. With an IP40 rating, it should be installed inside a suitable enclosure or control cabinet, not exposed directly to rain or dust.
Share your thoughts with other customers
WhatsApp us
Reviews
There are no reviews yet.